Addressing Compliance Challenges with Data Centers

At the Aug 27 SEAC general meeting, Chris Jensen, the UL Solutions Director of Codes and Regulatory Services, spoke about grid infrastructure impacts from the evolving data center landscape, power and electrical safety issues with data center deployment, and how developing codes and standards will support the safe adoption of new technologies.

While the presentation was intended for SEAC general meeting attendees only, UL Solutions has provided us with a recent episode of its Code Authority video series where Jensen also discusses data center deployment. Read on for a summary of Jensen’s SEAC presentation to accompany the Code Authority video, which also features SEAC member Robert Marshall, Senior Regulatory Engineer at UL Solutions.

Evolving data center landscape

In 2025, more than 4,000 of the world’s 12,000 data centers were in the US. Virginia, Texas, California, Illinois, Georgia, and Ohio lead among states with the most deployments. Jensen noted that while industry and government leaders sometimes talk about the race to keep up with China, only about 300 data centers have been deployed in China. The US is leading the way in confronting data center deployment impacts on electric grid infrastructure.

Artificial intelligence (AI) and high-density computing applications are leading engineers to reimagine power supply hardware in a holistic fashion, or as Jensen says, from chip to grid. Rather than the traditional architecture using information technology (IT) racks linked to halls and power rooms by 415 Vac busways, we’re now seeing data center designs with IT racks linked to multiple overcurrent protection by 800 Vdc conductors.

Jensen says 800 Vdc is here now, 1,500 Vdc is on the horizon, and energy storage systems (ESS) are a natural fit for data centers. Superconductors also are under development due to inherent challenges with DC voltages.

Power and electrical safety

The technology changes driven by data center deployment require us to take a fresh look at loads, grid infrastructure, and the relevant codes and standards.

For example, increased power requires novel cooling techniques. Jensen says air-to-air cooling is no longer adequate in data center applications as it was with legacy IT systems. Liquid-to-air cooling (using a liquid coolant to absorb heat from equipment), liquid-to-liquid cooling (using multiple liquid coolant loops through a heat exchanger), and immersion cooling (submerging equipment into a coolant that does not disrupt electrical performance) are potential alternatives. So is direct-to-chip cooling, which circulates coolant through cold plates mounted directly onto high-heat components.

The transition to 800 Vdc also introduces new safety considerations. Anytime you replace alternating current with direct current, for starters, it becomes more difficult to break the circuit. DC power systems require a different approach to staff training, including for emergency responders, to use the correct personal protective equipment (PPE) and minimize risk of arc-flash incidents. Hot swapping (replacing equipment while power is up and running) also needs to be reconsidered in DC power systems.

Adapting codes and standards

Jensen says 32 UL standards already cover 800 Vdc. Revisions are being pursued for 21 standards that do not cover 800 Vdc including standards for distribution equipment, power supplies, power converters, overcurrent protection devices, grounding and bonding equipment, connectors, cables, and more. Future gap analysis is needed for 1,500 Vdc power.

Technical committees overseeing UL standards are also developing and updating approved processes for superconductors, more flexible cables (addressed by UL 2137, an outline of investigation looking at Data Center Power Cables), and AC/DC power whips (addressed by another outline of investigation, UL 817A). Liquid-cooled cables and assemblies are another area of exploration drawing interest from industry and test labs.

Data center code development activities are also underway with two National Electrical Code (NEC) task groups that have charters to impact data centers, the NEC Correlating Committee Data Center Task Group and the NEC Correlating Committee Direct Current Task Group. NFPA is also convening a correlating committee, Code-Making Panel 12, to look at gaps affecting data centers in the 2029 code cycle. As for International Code Council development activities, the Fire Code Action Committee and the Building Code Action Committee have working groups that will likely consider issues affecting data centers.Jensen encourages SEAC members to get involved and help shape future codes and standards. 

Joining SEAC General Meetings

You may register for each Monthly General Meeting using the online form below. Upon registration, you will receive a confirmation email that contains a unique meeting link, which can be used to automatically join future meetings.

If you have previously attended a SEAC General Meeting, then you have already been added to a recurring Google Calendar invite with the registration link. You may also select “Add to Calendar” from your unique confirmation email for quicker access. Please feel free to reach out if you have any questions.  